Sizing, Fuelling and Servicing a Gas Generator Set on Saudi Industrial Sites
A gas generator set pairs a spark-ignited engine with an alternator and runs on natural gas or LPG. For plants with a reliable gas supply it offers lower emissions than diesel and, in many cases, lower fuel cost per kilowatt-hour. It also behaves differently from a diesel set in ways that affect sizing, starting and maintenance, which is where most specification mistakes happen. This guide walks through the decisions in the order a project team usually meets them.
How a gas generator set works
The engine burns a gaseous fuel in an internal combustion cycle, and the alternator turns that mechanical power into alternating current. An electronic control module watches temperature, pressure, speed and output, and adjusts the fuel and air mixture to hold voltage and frequency within limits. Because gas burns cleaner than diesel, there is less soot in the exhaust, and oil change intervals are often longer, though the engine still needs regular attention to its ignition system and air intake.
Selecting the size and fuel type
Sizing starts with a load analysis. List every item that must run during an outage or as part of normal operation, note its rating in kW and kVA, and record the starting current of the large motors. Add a margin for future load. Then check the manufacturer's derating figures for your site, because output falls as ambient temperature rises, and Saudi summer temperatures on an exposed site can sit well above the reference conditions on the datasheet.
Gas engines generally accept smaller load steps than diesel engines. A large motor or a block of load switched on at once can be too much for a gas set, so plan staged starting, soft starters or variable frequency drives, and ask the supplier for the step-load figures in writing.
Fuel choice follows the site:
- Natural gas suits plants with a pipeline connection. Check the supply pressure and the gas quality, since heating value and composition affect output and engine settings.
- LPG works where there is no pipeline, but it needs storage tanks, vaporisers and a delivery arrangement, and the tank size sets how long the set can run without a refill.
- Dual-fuel configurations exist for some engines and give a fallback if one fuel is interrupted. Confirm the exact arrangement on the datasheet.
Connecting the set to your electrical system
A generator rarely works alone. For standby duty it connects to the main distribution board through an automatic transfer switch, or ATS. The ATS detects the loss of utility supply, signals the set to start and moves the load across once voltage and frequency are stable. The Generators & Transfer Switches service covers the generator, the ATS, the control panel and the integration between them, and the Automatic Transfer Switches product page lists the switch options.
Where several sets share a load, they need a synchronising panel and load-sharing controls. Where a set will run in parallel with the utility network, the network operator's approval is required before commissioning. If the building has isolated power panels for critical areas, the generator supply is usually arranged so that these loads are fed first and kept separate from non-essential equipment.
The physical installation matters as much as the electrical one. Plan combustion air, exhaust routing, ventilation of the plant room, acoustic treatment where neighbours or occupied spaces are close, and gas piping with leak detection. Gas supply areas carry their own safety and area classification requirements, so involve the safety engineer early.
Testing and commissioning
Before handover a generator set should be proven under load, not just run on no load. A resistive load bank lets the commissioning team step the set up to its rated output, confirm cooling and exhaust temperatures, and check voltage and frequency response. Load Banks are also used for periodic testing, because sets that run lightly or rarely can develop problems that only show up at higher load.
Maintenance that keeps a gas set reliable
Follow the manufacturer's schedule by running hours, and keep a log. The items that matter most on a gas engine are:
- spark plugs and ignition components, which are replaced at set intervals;
- valve clearances and, where fitted, the turbocharger and its air system;
- oil level, oil condition and filters, ideally with periodic oil analysis;
- coolant condition, hoses and the radiator, which collect dust in the Saudi environment;
- air filters, which clog faster on dusty sites and may need more frequent changes during sandstorm season;
- gas train components, such as regulators and shut-off valves, and a check for leaks.
A standby set should also be started and loaded regularly, since a set that sits idle for months is the one that fails to start when the grid drops.
Choosing a supplier
Ask for a supplier that can cover the equipment, the engineering, the installation and the after-sales service as one package, and ask to see the load calculation behind the proposed set. NLS Power's range includes Industrial Generator Sets and Gas Generators, and a site survey is the first step to a proposal that names the model, the ATS arrangement, the wiring diagrams and a project schedule. The offer states the lead time for the specific set, so compare it across quotations rather than relying on a general figure.
FAQ
How quickly does a gas generator start and take load?
Standby sets are commonly specified to reach rated voltage and frequency within roughly ten seconds, but the figure depends on the engine, the controls and the ambient conditions. Take the exact value from the datasheet and from the supplier's step-load data.
Can a gas generator run on both natural gas and LPG?
Some engines are offered in dual-fuel or fuel-flexible versions, and others are built for one fuel only. The datasheet states which fuels the engine is approved for, and the control settings usually differ for each.
How often should a gas generator be serviced?
Follow the manufacturer's schedule by running hours, and add checks after heavy dust or sandstorm periods. A standby set also needs regular test runs under load so that faults appear during a test and not during an outage.
Can generator performance be monitored remotely?
Many modern generator controllers support remote monitoring over common industrial protocols such as Modbus, so alarms, run hours and fuel use can be viewed from a control room. Confirm the communication options when you write the specification.
Related products

Automatic Transfer Switches
An automatic transfer switch (ATS) detects a utility power failure and switches the electrical load to a standby generator without manual intervention, then switches back once utility power is stable. NLS sources ATS panels from 100A to 4000A for hospital, commercial, and industrial projects across Saudi Arabia, built to IEC 60947-6-1 and sized to NFPA 110 transfer-time requirements where emergency power applies.

Load Banks
A load bank applies an artificial electrical load to a generator so it can be tested at or near its rated output without connecting to the site's actual electrical load. NLS sources resistive and reactive load banks for genset commissioning, acceptance testing, and NFPA 110 monthly load testing on projects across Saudi Arabia.

Industrial Generator Sets
Industrial generator sets provide essential power for demanding operations, from critical backup to continuous prime power. NLS Power supplies a wide range of reliable generator solutions tailored for sectors like oil and gas, manufacturing, and data centers, ensuring your operations remain powered efficiently and safely.

Gas Generators
Gas generators burn natural gas or LPG instead of diesel to drive an AC alternator, suited to continuous or prime duty wherever a gas supply already reaches the site. NLS sources gas generator sets from 20kVA to 2000kVA for industrial and commercial projects across Saudi Arabia, rated to ISO 8528, with lower fuel-storage overhead than an equivalent diesel set.