NLS Power
Oil-Immersed Transformers

Oil-Immersed Transformers

Oil-immersed transformers use mineral oil or synthetic ester both to insulate the windings and to carry heat away, which makes them more efficient per kVA than a dry-type unit at the same rating. NLS Power supplies oil-immersed transformers built to IEC 60076, in ONAN and ONAF cooling classes, for outdoor SEC-connected substations across Saudi Arabia.

Oil-immersed transformers use mineral oil, or increasingly synthetic or natural ester fluid, as both the winding insulation and the cooling medium. The oil circulates past the core and coil, picks up heat, and gives it up through radiators, either by natural convection (ONAN) or with fans forcing air across the radiators (ONAF) when the load needs a higher rating from the same tank. Larger transmission-class units add oil pumps (OFAF or ODAF) to move the fluid itself, though that scale sits above what most commercial and industrial Saudi projects specify.

Because the fluid is combustible, an oil-immersed unit needs an outdoor location or a dedicated fire-rated substation room, an oil-retention pit or bund sized to the full oil volume, and separation distances from occupied buildings that a dry-type unit doesn't require. In exchange, oil-immersed transformers run cooler for a given core and coil size, handle short-term overload better, and are generally the lower-cost option at ratings above roughly 1000kVA, which is why SEC-connected outdoor substations on industrial and utility-scale projects default to this type.

Vector group is almost always Dyn11 for SEC LV distribution duty, and the connection approval process will specify no-load and load loss limits, since a transformer's core loss runs continuously for the full life of the installation regardless of connected load. That steady loss is what drives lifetime energy cost more than the load loss does on a lightly loaded unit. Tap changers, off-circuit as standard or on-load where voltage regulation is needed, let the secondary voltage be trimmed to actual site conditions rather than the nameplate value.

Coastal sites near Jubail or Yanbu need extra attention to tank coating and radiator material, since salt-laden air corrodes standard paint systems faster than it does inland. NLS sources oil-immersed transformers against the rating, cooling class, vector group and loss class an SEC connection or project spec calls for.

Specifications

  • ✓Insulation and cooling: mineral oil or ester fluid, natural or forced circulation, per IEC 60076-2
  • ✓Cooling classes: ONAN standard, ONAF for a higher rating on the same tank, OFAF on larger units
  • ✓Vector group: Dyn11 standard for SEC LV distribution, other groups available for step-up or special duty
  • ✓Tap changer: off-circuit as standard, on-load tap changer (OLTC) where automatic voltage regulation is specified
  • ✓Installation: outdoor or dedicated fire-rated room, with an oil-retention pit or bund sized to full oil volume
  • ✓Loss class: no-load and load loss limits set against IEC 60076-20 efficiency tiers or the SEC connection spec

Frequently Asked Questions

Is an oil-immersed transformer more efficient than a dry-type unit?+

Generally yes, at the same kVA rating an oil-immersed unit runs lower no-load and load losses than a comparable dry-type transformer, mainly because oil is a more effective heat-transfer medium than air. The gap narrows at smaller ratings, and the dry-type's indoor-siting advantage often outweighs the efficiency difference on space-constrained sites.

Why does no-load loss matter more than load loss over a transformer's life?+

No-load loss (core loss) runs continuously for as long as the transformer is energized, whether or not it's carrying load, so it accumulates over the full installation life. Load loss only applies when current is flowing, so a unit sized with margin above its typical load carries a fixed core-loss cost that a loss-class spec is meant to control.

Can an oil-immersed transformer go inside a building in Saudi Arabia?+

Only in a dedicated fire-rated substation room built with an oil-retention pit or bund sized to the transformer's full oil volume, fire separation from occupied areas, and ventilation for the ambient the room will actually see. Most Saudi projects still default to outdoor siting for oil-immersed units where the plot allows it.

Related products

Cast-Resin Transformers

Cast-Resin Transformers

Cast-resin transformers encapsulate the windings in epoxy resin under vacuum, a dry-type construction that resists moisture and dust without a separate enclosure. NLS Power sources and supplies cast-resin units built to IEC 60076-11 for hospitals, data centres, metro stations and coastal or dusty sites across Saudi Arabia where a conventional dry-type winding would need extra protection.

Package Substations

Package Substations

A package substation combines MV switchgear, a transformer and an LV panel inside one factory-built, weatherproof enclosure, delivered to site as a single tested unit rather than assembled from separate equipment. NLS Power sources and supplies package substations built to IEC 62271-202 for compounds, labor camps, retail and industrial sites across Saudi Arabia, reducing on-site civil and electrical work.

Unit Substations

Unit Substations

A unit substation assembles MV switchgear, transformer and LV switchboard as coordinated equipment for a building's own electrical room, rather than a free-standing outdoor kiosk. NLS Power sources and supplies unit substations for high-rise towers, hospitals and industrial plants across Saudi Arabia, engineered so protection settings between the MV and LV sides are coordinated before equipment reaches site.

Ring Main Units (RMUs)

Ring Main Units (RMUs)

A ring main unit is a compact MV switchgear panel, usually three-way, that loops a medium voltage ring between substations so a fault on one section can be isolated without cutting power to the rest of the loop. NLS Power sources and supplies RMUs built to IEC 62271-200 for compound, industrial park and campus distribution networks across Saudi Arabia.

Auto-Transformers

Auto-Transformers

An auto-transformer shares a single winding between primary and secondary instead of using two fully isolated windings, which makes it smaller, lighter and lower-loss than a two-winding transformer of the same rating for a modest voltage change. NLS Power sources and supplies auto-transformers built to IEC 60076-1 for voltage step and interconnection duty on Saudi transmission and industrial projects.

Transformer Protection Relays

Transformer Protection Relays

Transformer protection relays detect internal and external faults, differential, restricted earth fault, overcurrent and temperature, and trip the transformer's circuit breakers before a fault causes structural damage or spreads to the wider network. NLS Power sources and supplies numerical protection relays with IEC 61850 communication for transformers on SEC-connected and industrial substations across Saudi Arabia.

Guides

Available in

Get in touch

Send us your RFQ

Tell us what you need and we will come back with pricing and lead times.

+966 53 590 8101